|
AFSA
Responds to Omega Sprinkler Reports
For
Immediate Release
Contact:
D'Arcy Graham at 214-349-5965
[DALLAS,
TEXAS - AUGUST 13, 1997] Reacting to published reports about
failures of Omega fire sprinklers produced by Central Sprinkler
Corporation, the American Fire Sprinkler Association expressed
concern that misrepresentations in the media may undermine
confidence in automatic fire sprinkler systems.
"We
are surprised at these sudden inflammatory media stories
about Omega sprinkler failures. This problem was announced
months ago by Central Sprinkler Corporation and it affects
only a small number of installed sprinklers," said Steve
Muncy, president of the American Fire Sprinkler Association.
"The manufacturer has been working with testing laboratories
to address and solve the problem," he added.
The
failure rates quoted in the media imply that a large number
of these sprinklers would fail in a fire situation. In an
Underwriters Laboratories' test of 800 Omega sprinklers,
69 percent of the sprinklers tested operated at 5 psi. Many
others operated within a range that would not constitute
an absolute "sprinkler failure," even though they did not
operate within the 7 psi for which the sprinklers are listed.
Eighty percent operated at 40 psi or less, which means they
would have operated under normal water pressure conditions.
In
a telephone conversation today, Central's President George
Meyer stated emphatically that, contrary to published reports,
the affected sprinklers are not the result of improper installation.
Earlier
reports from Central indicated the sprinklers could be affected
by cutting oil in the system or an introduction of stop-leak
type additives into the water supply, an additive prohibited
by standards for installation of automatic fire sprinklers.
"Use
of cutting oil has been an accepted practice in this industry
for many years and has never before presented a problem
in sprinkler systems. This is definitely not a problem of
installation, but a problem related to the reaction of the
older Omega sprinklers with compounds in the water supply,"
said Steve Muncy.
"I
don't know of any professional fire sprinkler contractor
that would use stop-leak type additives in the installation
of sprinkler systems," Muncy added, noting that the integrity
of the system could be compromised after installation.
Central
Sprinkler has been working with Underwriters Laboratories
to address the problem. They request sprinkler contractors,
building owners or system inspectors who know of a building
with Omega heads installed contact the manufacturer at 1-800-523-6512.
Samples can be sent to Underwriters Laboratories for free
testing.
Robert
McCullough, president of AllSouth Sprinkler Company in Lilburn,
Georgia and chairman of the American Fire Sprinkler Association,
stated that people must keep this issue in perspective and
remember that automatic fire sprinklers are still the best
method available to protect lives and property from fire.
"Although
this is indeed a serious situation, it is important to remember
that only a portion of a single model of automatic fire
sprinklers have failed, and then only under unusual circumstances.
Some sprinklers that were listed as 'failures' actually
operated, but at a higher pressure than that established
for the Omega sprinkler. In the event of a fire, the chance
of these sprinklers controlling the fire is extremely high.
Proper testing by UL and Central Sprinkler and replacement
when necessary should be done immediately, without panic,"
he said.
Established
in 1981, the American fire Sprinkler Association is a non-profit,
international association representing the open shop fire
sprinkler contractor. AFSA is dedicated to the educational
and professional advancement of the automatic fire sprinkler
industry.
|